An ISO 9001 : 2000 Certified Company
Home about us Product Our Client Contact Us feedback Site Map
Alarm Annunciators, Electronic Components, Process Control Instruments, Industrial Automation System, Microprocessor Based A.C. Controllers, Timers, Preventers, Microcontroller Based A.C. Controllers, Digital Panel Meters, Current Scanners, Digital Temp.Indicators & Controllers, Motor Protection Relays, Custom Built Electronic Equipments, RPM / Frequency Indicators, Line Frequency Meters, AC VoltMeters, AC Ammeter, Voltage Scanner, Humidity Indicators
 
 
Manufacturers of :
Microprocessor based A.C. Controller
Chiller Controller
Microprocessor based Alarm Annunciator
Compressor Guard
Digital Panel
Digital 3-Phase Auto Voltage/Current Scanner
Motor Protection Relays
Digital Panel Meter
AC / DC Power Monitor
Line Frequency Meter
AC Voltmeter
Voltage Scanner
Scanner
Temperature Indicator
A.C. Controller for ATM
Annunciator Fascia
Electronic Hooter
Electronic Timer
Audio-Visual Panel for Tel. Exchange Meters
Digital Temperature Indicators / Controllers
Custom Built Electronic Equipments
VAF Meters
RPM / Frequency Indicator
AC Ammeter
Three Phase / Single Phase Voltage Monitor
Process Indicator
Humidity Indicator
Fire Protection Panel
 
 
 
 
Phase Correction Relay :
Protection of 3 Phase devices against Over voltage,Under voltageor unbalance supply is one of the major issue in electrical systems.

For safe running of 3-phase devices, special protections that keep a continuous watch on supply conditions are very essentials. The major cause of maxium load burn-out is overloading which occurs due to unbalance supply

'PROTONs PHASE CORRECTOR RELAY' offer following protections along with 3 digit display showing R-Y,Y-B,BR voltages in scanning mode with precise accuracy.

LOW/HIGH voltage tripping to ensure trouble free running of 3-phase Loads. Single phasing & Unbalance protection.
Phase correction RELAY 'R2' which operates only when phase
sequence changes.
Phase Correction Relay
 
SALIENT FEATURES :
Microcontroller based technology
Voltage protection along with digital voltage readout.
Wide range of supply variation.
Protection against Under voltage.
Protection against Over voltage.
Phase unbalance protection.
All the set points setable by keys.
Indication unaffected by meter mounting position.
Indications for High voltage, Low voltage ,SPP & Relay ON .
Separate phase corrector relay.
Hold feature:- Press INC key in Running condition to observe particular supply voltage.
 
TECHNICAL SPECIFICATION :
Supply Voltage
300-500 VAC, Three phase (No auxilliary supply)
Output Contacts
: PHASE O/P1 FOR R-Y-B SEQUENCE CONTACTOR1
: PHASE O/P2 FOR REVERSE SEQUENCE CONTACTOR2
Voltage trip setting
: 420 to 500 V For OV with digital display (resolution of 1 V)
: 300 to 380 V For UV with digital display (resolution of 1 V)
( Hysterisis between cut off & cut in is 10V )
Trip Time delay
For OV,UV, SPP,Reverse phasing,Imbalance in supply 10 msec.
NOTE: System supply is taken from R & N If R phase goes off then unit will be off.
ON Delay
Selectable by keys from 1 to 60 sec.
Reset Mode
Auto reset.
Indications
UNDER VOLTAGE : RED LED
OVER VOLTAGE : RED LED
RELAY 2 ON : GREEN LED
RELAY 1 ON : GREEN LED
Keys
 [ FUN ] FUNCTION key, To select a set point function.
 [ /\ ] INC key, To increment set point.
 [ \/ ] DEC key, To Decrement set point.
Operating Temperature range
-5 0C to 60 0C.
Relative Humidity
95%
Mounting
DIN RAIL mounting.
 
Working :
In the normal run mode, display shows Voltages Vry,Vyb,Vbr for 10 sec. each If the supply is within the range (No faults)then display shows count down for time set in the set point ( default 10 sec) & after that Relay will be ON. If OV/UV/SPP/Reverse Phase or unbalance occurs in the supply then Relay will be OFF & corresponding fault LED starts blinking.Hysterisis betwen Cut off & cut in is 10V for OV & UV. Note that for SPP & Unbalance LED is not blinking but message appears on display at end of scanning. but display shows particular fault"rP" at the end of scanning.All the faults are indicated by message.

If phase reversal occurs then Relay 1 will be off & after time delay Relay 2 will be ON.
If phase sequence is Ok then again Relay 1 will be ON.
OV,UV,SPP is applicable for both relays

 
SET POINTS :
- To set Under voltage set point press FUN key once,display shows 'uV' again press FUN key then the set point is viewed (default 350V)now user can set the
UV set point using arrow keys.

- To set Over voltage set point press FUN key till display shows 'oV' again press FUN key then the set point is viewed(default 460V) now user can set the OV set point using arrow keys.

- To set On delay set point press FUN key till display shows 'dly' again press FUN key then the set point is viewed(default 10sec.)now user can set the

on time for relay using arrow keys.
To decide maximum imbalance tolerable between phase voltages(Imbalance set point) press FUN key till display shows 'ub' again press FUN key then the set point is viewed(default 40V)now user can set imbalance set point using arrow keys.

SET POINTS:

IMP.NOTE: After set point entered,the system goes into Run mode
automatically after 5 sec.The setpoint is stored automatically.
also if a set point is changed & FUN key pressed again then also
set point is saved in memory.