An ISO 9001 : 2008 Certified Company
Home about us Product Our Client Contact Us feedback Site Map
Alarm Annunciators, Electronic Components, Process Control Instruments, Industrial Automation System, Microprocessor Based A.C. Controllers, Timers, Preventers, Microcontroller Based A.C. Controllers, Digital Panel Meters, Current Scanners, Digital Temp.Indicators & Controllers, Motor Protection Relays, Custom Built Electronic Equipments, RPM / Frequency Indicators, Line Frequency Meters, AC VoltMeters, AC Ammeter, Voltage Scanner, Humidity Indicators
 
 
Manufacturers of :
 
 Microprocessor Based A.C. Controller
Sensicool Controller
Damper Controller
Cell Site Controller
Microprocessor Based Alarm    Annunciator
Digital Panel Meters
Digital 3-Phase Auto Voltage /    Current
Scanner
Motor Protection Relays
Digital Panel Meter
AC / DC Power Monitor
Line Frequency Meter
AC Voltmeter
Voltage Scanner
Temperature Indicator
A.C. Controller for ATM

Single Phase Preventer 1
Single Phase Preventer 2
Frequency Monitoring Relay
Phase Correction Relay
Digital Temperature Indicators /    Controllers
Winding Protection Rrelay
Phase Selector Relay
Earth Fault Relay
VAF Meters
RPM / Frequency Indicator
AC Ammeter
Three Phase / Single Phase Voltage    Monitor
Process Indicator
Humidity Indicator
Fire Protection Panel
 
 
 
 
 
Fire Panel
A fire alarm control panel is an electronic panel that is the controlling component of a fire alarm system. The panel receives information from environmental sensors designed to detect changes associated with fire, monitors their operational integrate and provides for automatic control of equipment. The panel gives electrical energy to operate any associated sensor, control and relay. Fire detection is done using fire sensor. The micro controller based panel shows room temperature on seven segment display, sense fire faults of zones and controlling the alarm relay outputs
Fire Panel
 
 
 
Features :-
Microcontroller based design.
Two zone panel.
Dual Power supply 230 V AC and 48 V DC.
LED Indication for each zone & fire fault.
Relay output for
1) Common Fault
2) High Temp
3) Door Open
4) Fire Faults
Test key to test LEDs, sounder and relays output.
Isolate control switch on front panel to enable Mute sounder, Test and Reset Keys.
Power ON LED indication on panel.
Digital display of Temperature & set point.
Vertical Wall mounting Panel design.
A smoke / Fire sensor operates on 24 V DC associated with panel.
Powder coated cabinet.
 
Technical Specifications :
1. Supply Voltage
1. 230 V AC  +/- 15%.
2. 48 V DC
2. Relay
Coil- 12 V DC , contacts  NO/NC with 10 A current capacity
3. Buzzer
12 V DC
4. Isolated switch
12 V DC.
5. Fire sensor

24 V DC

6. Door Open switch
24 V DC
7. Dimensions
305(L) x 85(W) x 215(H) mm
 
Connection Diagram
   
 
Connection Diagram
 
Working :
   
 

In normal working condition system is silent. Only ‘HEALTHY’ indication is flashing. Fire panel needs both 230 V AC and 48 V DC power input . If any one of them is absent AC/DC Power fault is appears. Room temperature is display on seven segment display. User has 3 keys FUN, Up arrow(  ), Down Arrow(  )  to change the room high as well as room temperature offset. To adjust the room temperature press FUN key 5 times continuously then using UP arrow & down Arrow Room temperature is adjusted.

            Fire detection is done using smoke sensor. The smoke detector comes with blinking LED to indicated status of sensor. Once the fire condition is removed the LED and buzzer are reset. The Fire panel has 4 modes of operation:
 
POWER
During power ON condition ‘HEALTHY’ green LED indication is continuously flashing.
FAULT :

There are 5 LEDs on front panel to show the fault relay status.

 

COMMON:

The Amber LED is  flashing during any faults appears in the system. At the same time corresponding fault relay is ON

ZONE 1:

If Fire detection is done using smoke sensor of Zone 1 , the corresponding  amber LED is flashing. At the same time corresponding fault relay is ON


ZONE 2:

If Fire detection is done using smoke sensor of Zone 2 , the amber LED is flashing. At the same time corresponding fault relay is ON

DOOR OPEN:

If door open fault detection is done using door open switch, the corresponding  amber LED is flashing. At the same time corresponding fault relay is ON

AC/ DC POWER:

Any one of power input is fail detection is done, the corresponding amber LED is flashing. At the same time corresponding fault relay is ON

FIRE
There are another 3 Red LEDS for COMMON, ZONE 1, ZONE 2
 

COMMON:

The Red LED is flashing during ZONE 1 or ZONE 2 faults appear in the system.

ZONE 1:

If Fire detection is done using smoke sensor of Zone 1 , the corresponding  RED LED is flashing.

 ZONE 2:

If Fire detection is done using smoke sensor of Zone 2 , the Red LED is flashing.
CONTROLS : There are 3 control keys and one isolate control switch
 
ISOLATE CONTROLS:

On front panel there is 3 way key operated switch having green, yellow and red mark on the same. If key position is on Yellow mark the MUTE SOUNDER, TEST & RESET keys control are enable. If  key position is on Green & Red mark the MUTE SOUNDER, TEST & RESET keys control are Disable

MUTE SOUNDER:

Normally whenever fault appears the corresponding LED is flashing and Sounder is ON. By using MUTE SOUNDER key SOUNTER is SILENCE for one minute. Assume ISOLATE switch is on Yellow mark.

TEST:

To check the LED, Relay & Sounder output, Hold TEST key for some time. When TEST key is release the LEDs are OFF and after one minute Relays are OFF

RESET:
All faults Relay are OFF while pressing RESET key